Description
- Place of Origin: China (Mainland)
- Brand Name: HN electric
- Model Number: SafeClad
- Type: Gas-insulated
- Rated Voltage: 11/22kV
- Rated current: 630A
- Standard: IEC /ANSI Standard
- Power frequency withstand voltage: 70kV
- Lightning impulse withstand voltage: 170kV
- Certificate: ISO9001
- Usage: Electricity Transmission Project
SF6-insulated ring main unit and SF6-insulated compact switchgear are used in medium voltage distribution networks. They offer a sealed stainless steel tank which contains all the live components and switching functions. The transformer is protected either by a switch fuse combination or a vacuum circuit breaker.
SF6-insulated ring main unit can be supplied as a 2, 3 or 4-way unit in standard configurations with additional equipment according to customer specification.
SF6-insulated compact switchgear has a unique flexibility due to its extendibility and the possible combination of fully modular and semi-modular configurations, with a maximum of 5 modules in one SF6-tank.
The units are delivered from the factory ready for installation. Routine tests are carried out on all units/ modules before dispatch. No special tools are required for installing the equipment.
ELECTRICAL DATA
|
Gas Insulated Switchgear
|
C-module
|
F-module
|
V-module
|
|
Switch
disconnector
|
Earthing switch
|
Switch-fuse
combination
|
Earthing switch
|
Vacuum
circuit-breaker
|
Earthing switch
|
|
Rated voltage
|
kV
|
12/17,5/24
|
12/17,5/24
|
12/17,5/24
|
12/17,5/24
|
12/17,5/24
|
12/17,5/24
|
|
Power frequency withstand voltage
|
kV
|
28/38/50
|
28/38/50
|
28/38/50
|
28/38/50
|
28/38/50
|
28/38/50
|
|
Impulse withstand voltage
|
kV
|
95/95/125
|
95/95/125
|
95/95/125
|
95/95/125
|
95/95/125
|
95/95/125
|
|
Rated current
|
A
|
630/630/630
|
|
2001)
|
|
200/200/200
|
|
|
Breaking capacities:
|
|
|
|
|
|
|
|
|
--active load
|
A
|
630/630/630
|
|
|
|
|
|
|
--closed loop
|
A
|
670/670/670
|
|
|
|
|
|
|
--off load cable charging
|
A
|
141/141/141
|
|
|
|
|
|
|
--off load transformer
|
A
|
|
|
20/20/20
|
|
|
|
|
--earth fault
|
A
|
205/160/160
|
|
|
|
|
|
|
--earth fault cable charging
|
A
|
117/91/91
|
|
|
|
|
|
|
--short-circuit breaking current
|
kA
|
|
|
see 2)
|
|
16/16/16
|
|
|
Making capacity
|
kA
|
52,5/40/40
|
52,5/40/40
|
see 2)
|
12,5/12,5/12,5
|
40/40/40
|
40/40/40
|
|
Short time current 0,5 sec 3)
|
kA
|
|
|
|
|
16/16/16
|
|
|
Short time current 1 sec 4)
|
kA
|
|
|
|
5/5/5
|
16/16/16
|
|
|
Short time current 3 sec 5)
|
kA
|
21/16/16
|
21/16/16
|
|
|
|
16/16/16
|
Note: 1) Depending on the current rating of the fuse-link
2) Limited by high voltage fuse-links
3) Maximum rating for bushings Interface A (200 series plug-in)
4) Maximum rating for bushings Interface B (400 series plug-in)
5) Maximum rating for bushings Interface C (400 series bolted)

Hunan Union Electric Corp.
Year Established:2015
Business Type:Manufacturer, Trading Company
Management Certifiation:
Operational Address: Room 803, Yanggujinyuan, No. 39, Luhu Road, High-Tech Development Zone, Changsha, Hunan, China (Mainland)
Verified Supplier
Credit Check