Remove Now
Cancle

220kV three phase on load voltage regulator HV power transformer

We have adopted series of important reforms on the 220kV level there-phase oil-immersed on-load tap-changing transformer referring material,process and structure.The transformer has the features of small size,light weight,high efficiency,low loss,low noise,reliable operation etc.which can reduce a large amount of power network loss and operation expenses with significant economic benefits.

Description

Features:

1. Iron core is made of cold-rolled silicon-steel sheet with high conduction of magnetism and adopts pulling-plank structure,
so that its magnetic route is short, losses and noise level is low;
2. Compress wire is adopted for winding so losses are low and have good ability withstand short-circuit;
3. Its active part adopts special pressing method which could ensure reliable axial pressure;
4. The oil tank is bell type with the structure of full folding plate type, having an excellent exterior and easy for maintenance;
5. Adopting capsule-type oil container, it can reduce oil aging to the lowest degree.
6. Amount of local discharged: The apparent discharge amount is less than 80pC under the 1.5 times of rated voltage;
7. Noise: Products of 63MVA and below is lower than 58dB(AN);
8. Power loss: no-load loss is 30% lower than that of IEC standard;
9. Reliability: All in-service product have no damages or oil leakage occurred;

environment condition
Device type:outdoor
Environment:Maximum temperature +40℃,minimum temperature -30℃
Altitude:≤1000 meters(>1000 meters,need to modify temperature rise)
Relative temperature:≤90%(25℃)
Installation area with no corrosive gas and obvious fouling etc.


Main Technical Parameters:

Rated power
(kVA)


High Voltage
(kV)


H.V Tap range


Low Voltage
(kV)


Connection Symbol


Short-Circuit Impedance
(%)


No-load Loss
(kW)


On-Load Loss
(kW)


No-load Current
(%)

9 Type

10 Type

11 Type

9 Type

10 Type

11 Type

31500

220
242

±8×1.25%
±8×1.5%

6.3,6.6,
10.5,11,
20,34.5,
35,37,
38.5,66,
69

YNd11

12~14

38

34

30

135

128

128

0.7

40000

45

41

36

157

149

149

0.63

50000

54

49

43

189

180

180

0.56

63000

63

57

50

220

209

209

0.56

90000

80

72

64

288

274

274

0.49

120000

99

89

79

346

329

329

0.49

150000

116

104

93

405

385

385

0.42

180000

135

122

108

468

445

445

0.42

 

 

 