Remove Now
Cancle

Automatic current and voltage test bench

 The device tests more than one bit transformer device is the company to adapt to the modern transformer check the rapid and accurate development of the characteristics of a new generation of transformer test equipment. 

Description

  The device tests more than one bit transformer device is the company to adapt to the modern transformer check the rapid and accurate development of the characteristics of a new generation of transformer test equipment. The device consists of HGQA-C transformer calibrator, FY98 load current and voltage transformer box, control cabinet, current transformers, special test bench, and several other components. In maintaining the technical characteristics of the original premise, the rapid measurement of the current transformer quickly locate the test points, and the load box, the transformer turns ratio coverage of various aspects has been greatly improved.

 

Environmental conditions

Temperature:5°C-40°C              Humidity:Less than80%(25°C) 

Altitude:Less than 2500mm       Power frequency:50Hz±0.5 Hz   

supply voltage:220V±5 V

Measuring range

With the phase component (%): 0.0001~200.0    Rresolution:0.0001

Orthogonal component (sub):0.001~700.0           Resolution:0.001

Impedance (Ω):0.0001~20.0                                 Resolution:0.0001

Admittance (ms):0.0001~20.0                               Resolution:0.0001

Basic errors

With the phase component: X=±(X*2%+Y*2%±2counts)

Orthogonal components: X=±(X*2%+Y*2%±5 counts)

                                      “X”,“Y”--- shows the value of equipment

                                        "5 words" equipment quantization error

Dial indicator:1.0degree

Output current, output voltage:1.0 degree

Scope of work 

Current:(1%-149%)In    (In =5A)   (5%-149%)In   (In =1A)

Voltage:(5%-149%)Un    (Un =100V,150V,100V/ )

             (5%-149%)Un    (Un =100V/3)

Workload

Current: TO on the TXLess than 0.12Ω       cosΦ=1

Voltage: a for x Less than 0.25VA       (100V)

Dimensions(cm)

670(L)×630(W) ×1570(H)

 


1  The unit uses high-power programmable technology, comprehensive technical indicators in the country first, so that more accurate positioning of test points, capacity of up to 7KVA;
2  The current transformer installed in more than just measuring the speed has been a qualitative improvement, in 3 minutes to measure any change in the ratio of twelve current transformer;
3  The device configuration of the 1A, 5A of the standard current transformer, the current configuration of the load box 1A, 5A load value 2.5VA-80VA, voltage load box equipped with 100V, 100 / √ 3 load value from 1.25VA-158.75VA meet Various user requirements. Load me in the measurements can be automatically switched.

Year Established:2006

Business Type:Manufacturer and Trading Company

Management Certifiation: ISO9001

Operational Address: No. 6, 2/F, Bldg. 3, Guannan Fuxing Medical Park, No. 62, Optical Valley Avenue, East Lake Development Zone, Wuhan, Hubei, China (Mainland)