Description
- Place of Origin: Beijing, China (Mainland)
- Brand Name: Daelim
- Model Number: LW25
- Type: High Voltage
- Poles Number: 3
- Rated Short-Circuit Breaking Current: 50ka
- Rated voltage: 550kv
- Rated frequency: 50/60Hz
- Rated current: 3150~4000A
- Standard: GB10963/IEC60898
- Brand: Daelim
- Certificate: IEC 62271-100
- Creepage Distance: 11000~17000mm
- Gas: SF6
- Color: Black&white
1.Brief Introduction
H.V. A.C.porcelain type SF6 gas circuit breakers, with voltage from 40.5-550kV and rated current up to 4000A, manufactured by our company, are provided with
three kinds of operating mechanism, pneumatic, spring and hydraulic type.
Motor is used in spring mechanism to charge closing spring and charge opening spring at closing. Disk spring is used in hydraulic mechanism to be charged instead
of traditional compressed nitrogen gas for charge, and hydraulic driving is used at both opening and closing. Compressed air is used in pneumatic mechanism as driven
force for open while spring is used for close. The three kinds of operating mechanisms have their own features and are used in circuit breakers of different voltage
class respectively.Due to the unit structure in circuit breaker, there are advantages of minimized number of breaks,lower number of parts, simple structure,high
reliability and long period of inspection.
2.Normal Service Condition
2.1.Altitude:≤3000m
2.2.Humidity monthly:≤90%
2.3.Max .wind velocity:≤35m/s
2.4.Pollution class:Ⅲclass,IV class
2.5.Ambient air temperature:-35℃~40℃(It’s satisfied under condition of -40℃ in heavy cold area)
2.6.Max .temperature difference daily: 25K
2.7.Earthquake withstand density:8 degree
2.8.Ice coating: ≤10mm
2.9.Max. radiance from sun: 1000 W/m2
Note: When product is used under the condition out of above range, user and manufacturer shall consult to confirm.
|
No.
|
Item
|
Unit
|
LW 550/Y
|
|
1
|
Rated Voltage
|
kv
|
550
|
|
2
|
Rated Frequency
|
Hz
|
50/60
|
|
3
|
Rated Current
|
ka
|
3150,4000
|
|
4
|
Rated short-circuit breaking current
|
ka
|
50,63
|
|
5
|
Rated short-circuit making current
|
ka
|
125,160
|
|
6
|
Rated short-time withstand current and duration
|
ka
|
50/63(3S)
|
|
7
|
Rated peak withstand current
|
ka
|
125,160
|
|
8
|
Closing time
|
ms
|
65-95
|
|
9
|
Opening time
|
ms
|
≤20
|
|
10
|
Breaking time
|
ms
|
≤40
|
|
11
|
Rated SF6 gas pressure (at 20°C)
|
mpa
|
0.60
|
|
12
|
Creepage Distance
|
cm/kv
|
2.0,2.5,3.1
|
|
13
|
Operating mechanism
|
|
Hydraulic
|
|
14
|
Applied standards
|
|
IEC 62271-100
|