Description
1.1 Wide measuring range :current 0.01A-100A,voltage:40V-480V
1.2 The measure ratio is about 2 to insure the meter has the highest accuracy in the measuring range.
1.3 Strong measuring functions: three phase four wires active energy, three phase three wires active energy, three phase three wires sine reactive energy, three phase four wire 90° reactive energy, three phase three wires 60°reactive energy.
1.4 Easy to operate: there are 5 operating buttons at the bottom of the screen, which are corresponding with the reminding symbols on the screen.
1.5 The standard meter has RS-232 communication interface, which can communicate with PC in two ways. It can transmit the measuring data to PC as well as measure automatically controlled by PC.
.jpg)
2.1 Input characteristics
2.1.1 Voltage input
Input range(V) 40—480
Input measuring range(V) 60、120、240、480
Overload Voltate(V)600
Input load ≤0.5mA(480V)
2.1.2 Current input
Input range(A) 0.01—100
Input measuring range(A)100、50、25、10、5、2.5、1、0.5、0.25、0.1、0.05、0.025
Overload current(A) 150
Input overload ≤0.2mΩ(100A—0.25A)
≤0.3Ω (0.25A—0.01A)
2.2 Output characteristics
2.2.1 Output frequency of pulse
f =C ·P/3600 (H )
f =f /10000 (H )
2.2.2 Output level:TTL level
2.2.3 pulse constant
Pulse constants table of high frequency Table 1.C (P/kwh)
|
|
100A
|
50A
|
25A
|
10A
|
5A
|
2.5A
|
|
480V
|
6.25×10
|
1.25×10
|
2.5×10
|
6.25×10
|
1.25×10
|
2.5×10
|
|
240V
|
1.25×10
|
2.5×10
|
5×10
|
1.25×10
|
2.5×10
|
5×10
|
|
120V
|
2.5×10
|
5×10
|
1×10
|
2.5×10
|
5×10
|
1×10
|
|
60V
|
5×10
|
1×10
|
2×10
|
5×10
|
1×10
|
2×10
|
|
|
1A
|
0.5A
|
0.25A
|
0.1A
|
0.05A
|
0.025A
|
|
480V
|
6.25×10
|
1.25×10
|
2.5×10
|
6.25×10
|
1.25×10
|
2.5×10
|
|
240V
|
1.25×10
|
2.5×10
|
5×10
|
1.25×10
|
2.5×10
|
5×10
|
|
120V
|
2.5×10
|
5×10
|
1×10
|
2.5×10
|
5×10
|
1×10
|
|
60V
|
5×10
|
1×10
|
2×10
|
5×10
|
1×10
|
2×10
|
Pulse constant of low frequency C =C /10000
2.3 Accuracy
2.3.1 Class :0.05 or 0.1
2.3.2 Accuracy of power measurement
Accuracy of active power measurement: 0.05%、0.1%(PF≥0.5)
Accuracy of reactive power measurement: 0.1%、0.2%(PF≥0.5)
2.3.3 Accuracy of energy measurement
Accuracy of active energy measurement:0.05%、0.1%(PF≥0.5)
Accuracy of reactive energy measurement:0.1%、0.2%(PF≥0.5)
2.4 Display
2.4.1 Items of display : three phase voltage : UL1、UL2、UL3(V)
Three phase four wires UL1、UL2、UL3 mean U 、U 、U
Three phase three wires U12、U23、U31 mean U 、U 、U
Three phase current IL1、IL2、IL3(A)
Active power:P(W)
Apparent power:S(VA)
Reactive power:Q(VA)
Power factor:Pf -1.0000—1.0000
Phase angle:θ(0°—360°)
Frequency of input signal:F(H )
2.4.2 Display digits:5 digits
2.5 Power supply: 220V±10%、50H ±5% Power consumption:About20VA
2.6 Pre-heated time: 30 min
2.7 Working circumstances :
Temperature: 5℃—40℃
Relative Humidity ≤85%
Noncorrosive gas
2.8 Outline dimensions:482mm×480mm×140mm
2.9 Net weight:About 10Kg