Kyn28A-12 MID-Set Type Metal-Clad and Metal-Enclosed Switchgear

KYN28A-12(GZS1-12Z) mid-set type metal-clad and metal-enclosed switchgear (hereinafter referred to as switchgear) is a new type product designed and developed by our company with domestic and international advanced technologies.

Description

  • Model NO.: KYN28A-12
  • Shell Material: Steel Plate
  • Structure: Cabinet
  • Trademark: HONLE
  • Specification: Rated frequency: 50HZ
  • HS Code: 8504401990
  • Certification: ISO9001
  • Installation: Fixed
  • Current: AC
  • Transport Package: Standard Export Carton
  • Origin: Zhejiang, China (Mainland)

KYN28A-12(GZS1-12Z) mid-set type metal-clad and metal-enclosed switchgear (hereinafter referred to as switchgear) is a
new type product designed and developed by our company with domestic and international advanced technologies, it is an
ideal upgrading product for replacing the old metal-enclosed switchgear such as KYN1-10, JYN2-10, GBC-10 and so on. Its
advantages as follows: 

 The cabinet shell is made of al-zinc-coated steel sheet, through CNC processing and multiple bending technique, then    assembled with bolts. It is featured with high mechanical strength, neat and elegant appearance, powder coating treated
door, good shock and corrosion resistance. Ingress protection level of the shell reaches IP4X. 

 Main switch of switchgear can be configured with VD4 vacuum circuit breaker and C3 series fixed type load switch from ABB corporation, also can be configured with many homemade vacuum circuit breakers (such as VS1, VH1, VK, ZN28) instead of overseas similar products. 

 No matter which circuit breaker selected, make sure that the air insulation distance of its bare conductor is larger than
125mm, and compound insulation is larger than 60mm. The breakers are featured with long service life, high parameters,
less maintenance, small size, etc. 

This switchgear is applicable for three-phase power grid of AC 50Hz and class 3.6~12kV, used for electric energy receiving
and distribution, it controls, protects and monitors the circuits, can be used in single bus and single-bus segment system or
dual-bus systems. This switchgear complies with IEC298 Alternating-current metal-enclosed switchgear and controlgear for
rated voltage above 1kV and up to and including 52kV , IEC694 Common specifications for high-voltage switchgear and controlgear, GB3906 Alternating-current metal-enclosed switchgear for rated voltage of 3~36kV, DL404 Indoor AC high voltage switchgear panel, DIN.VDE0670 Alternating-current switchgear for rated voltage above 1kV, etc. It enjoys perfect and reliable anti-misoperation function. 

 

Technical parameters of switchgear

Item 

 Unit

Data

Rated voltage
Rated frequency 
Rated current of circuit breaker
Rated current of switchgear
Rated peak withstand current (4s)
Rated peak withstand current (peak)
Rated short-circuit breaking current 
Rated short-circuit making current (peak)

 KV
 Hz
 A 
 A 
  KA 
       KA  

KA 

KA

 3.6,7.2,12
       50
       630,1250,1600,2000,2500,3150,4000 
       630,1250,1600,2000,2500,3150,4000 
       16,20,25,31.5,40,50,63 
       40,50,63,80,100,125,160 
       16,20,25,31.5,40,50,63 
       40,50,63,80,100,125,160

 Rated insulation level

1min power frequency withstand voltage
       Lightning impulse withstand voltage

 KV
   KV 

 24
 40

 32
 60

 42
 75

 Protection class

The shell is IP4X, and it is IP2X when the compartment door and circuit breaker chamber door are opened

           


 Technical parameters of VD4 and VS1-12 vacuum circuit breaker 

Item

 Unit

 Data

Rated voltage
Rated frequency
Rated current of circuit breaker
Rated peak withstand current (4s)
Rated peak withstand current (peak)
Rated short-circuit breaking current
Rated short-circuit making current (peak)

 KV
       Hz
       A 
       A 
       KA 
       KA  
       KA 
       KA

 3.6,7.2,12
       50
       630,1250,1600,2000,2500,3150,4000 
       16,20,25,31.5,40,50,63 
       40,50,63,80,100,125,160 
       16,20,25,31.5,40,50,63 
       40,50,63,80,100,125,160

Rated insulation level

1min power frequency withstand 

 KV
       KV 

42
 75

Rated operating sequence
Rated short-circuit current breaking times
Mechanical life 

 
       Times
       Times

O-0.3s-CO-180s-CO
       50
       2000

       


Mechanical characteristics of VD4 and VS1-12 vacuum circuit breaker 
When the circuit breaker is used to control the motor of 3~10kV, must apply metal-oxide arrester if the starting current is smaller than 600A, details should be determined by both users and manufacturer through negotiation. When the circuit breaker is used to disconnect the capacitor bank, rated current of the capacitor bank should not exceed 80% of rated current of circuit breaker.

Item

 Unit

Data

Clearance between open contacts
Overtravel
Phase-to-phase central distance
Closing contact bounce time
Three-phase opening asynchrony

 mm
       mm
       mm 
       ms 
       ms

 11±1
       4±0.5 
       210±0.5,250±0.5,275±0.5  
       ≤2 
       ≤2

Breaking time at operating voltage of

  Max
       Rating
  Min

 ms
       ms

      ≤50
       ≤50
       ≤60

Closing time
Average closing speed
Average closing speed
Conductive circuit resistance
Contact pressure 

 ms
       m/s
       m/s 
       μΩ 
       N

      ≤100
       0.9-1.2
       0.6-0.8 
       ≤40 
       3200±100

       


Technical parameters of operating mechanism 

Item 

 Unit

Value

 Rated operating voltage

 Closing coil

 V

 DC220,110

 Closing coil

 V

 DC220,110

 Coil power

 Closing coil

 W

 245

 Closing coil

 W

 245

Power of energy-storage motor
Rated voltage of energy-storage motor
Energy-storage time

 W
       V
       S

 50
       DC220,110
   ≤10


Main technical parameters of ZN-12 (VHI) vacuum circuit breaker

 Item 

Unit

Parameter

Rated voltage
Rated frequency
Rated current
Rated short-circuit breaking current
Rated short-circuit making current
Rated peak withstand current
Rated short-time withstand current
Rated short-circuit duration
Rated breaking current of single capacitor bank
Rated breaking current of back-to-back capacitor bank
Power frequency withstand voltage
Lightning impulse withstand voltage
Rated short-circuit current breaking times
Mechanical life

      KV
       Hz
       A 
       KA 
       KA 
       KA 
       KA 
       s 
       A 
       A 
       KV 
       KV 
       Times
       Times

 12
       50
       1250 
       31.5 
       80 
       80 
       31.5 
       4 
       630 
       400 
       42 
       75 
       50 
       1000

Rated operating sequence

 

O-0.3S-CO-180s-CO

Opening time
Closing time
Control voltage 
Power of closing coil 
Power of opening coil 

      ms
       ms
       V 
       VA 
       VA

 


Normal service conditions

1.Ambient air temperature: -15ºC~+40ºC;

2.Relative humidity: daily mean not over 95%, monthly mean not over 90%;

3.Altitude: not exceed 4000m;

4.Seismic intensity: not beyond Ms8;

5The installation site should be free of fire, explosive danger, serious pollution, chemical corrosion or severe vibration.

Special requirements beyond above conditions should be determined by both users and manufacturer through negotiation.

 