Remove Now
Cancle

LB current transformer

It is outdoor, single phase and oil-immersed hair-pin type current transformer, which is used for metering and relay protection of 66kv, 110/132kv, 220kv 50/60Hz. Please contact us! Email:
liujing@mec.com.cn

Description

Email: liujing@mec.com.cn
Skype:liujingmec
MSN:lijing_0612@126.com
 
123123
It is outdoor, single phase and oil-immersed hair-pin type current transformer, which is used for metering and relay protection of 66kv, 110/132kv, 220kv 50/60Hz.
 
It is oil/paper insulation system, the primary insulation is wound from high voltage cable paper, and is placed several capacitor screen of voltage division in the primary insulation, which can improve electric field distributing and decrease the consumption of the insulation material. It will be immersed with transformer oil after desiccating vacuum. It has advantages of stable and reliable performance of insulation, rich successful experience, a long life time and convenient maintenance.
 
Perfect fluidity performance of transformer oil is good for heat dissipation. It also has self recover ability for the failure of partial discharge caused by air bubble and dust.
 
Item
Unit
LB5-66
LB6-110
LB7-220
Rated voltage
kV
66
110/132
220
Highest voltage
kV
72.5
126/145
252
Rated frequency
Hz
50/60
50/60
50/60
Rated transformation ritio
 
2×25~2×1000/5 or 1A
2×30~2×1000/5 or 1A
2×300~2×1000/5 or 1A
Number of secondary windings
 
1~5
1~6
1~8
Accuracy of measuring winding
 
0.2 0.2S 0.5 0.5S
0.2 0.2S 0.5 0.5S
0.2 0.2S 0.5 0.5S
Accuracy of protection winding
 
5P or 10P
5P or 10P
5P or 10P
Rated secondary output
VA
20~50
20~50
20~50
Creepage distance
mm
W1/1500
W2/1820
W3/2250
W1/2760
W2/3150
W3/3906
W1/5040
W2/6300
W3/7812
Power frequency withstand voltage
rms
140
185(230)(275)
395(460)
Lightning impulse withstand voltage
rms
325
450(550)(650)
950(1050)
 
 
 