VYGQ series vacuum circuit breakers can be integrated into air insulated switchgears, a perfect replacement for the sleeve type air insulated vacuum circuit breaker.

Description

  • Place of Origin: Guangxi, China (Mainland)
  • Brand Name: VYG
  • Model Number: VYGQ-40.5
  • Type: Vacuum
  • Poles Number: 3
  • solid insulated: circuit breaker
  • vacuum: 40.5kV

 

Specifications

1. IEC standards
2. ISO9000, ISO14000
3. 40.5kV Vacuum circuit breaker
4. Wthdrawable or fixed version, frontal

APPLICATION

 

VYGQ series vacuum circuit breakers are widely used in power plants, substations, petrochemical plants, metallurgical industries, mining, manufacturing industry, airport, subway, seaport and residential areas, etc.

 

VYGQ series vacuum circuit breakers can be integrated into air insulated switchgears, a perfect replacement for the sleeve type air insulated vacuum circuit breaker.

 

VYGQ series vacuum circuit breakers can run stably under following conditions:

1. Altitude: 3000~5000m

    While application at 2000m and above, please specify your conditions.

2. Ambient temperature:

    Max:                                      +40°C

    Daily average:                     ≤+35°C

    Min.:                                       -15°C

3. Humidity:

    Daily average RH:                  95%

    Monthly average RH:             90%

    Daily average saturated vapor pressure:         ≤2.2×10-3Mpa

    Monthly average saturated vapor pressure:    ≤1.8×10-3Mpa

4. Earthquake withstand ability: not exceed Grade 8

    Horizontal acceleration:

    Synthetic seismic wave                0.25g

    Sinusoidal wave                             0.15g

 

TECHNICAL FEATURES

 

1. Excellent performance

Electrical life: in compliance with Class E2 of circuit breaker, 274 operations in various short circuit currents.

Mechanical life: 30000 operations in compliance with Class E2 of circuit breaker

Capacitive current making/breaking capacity: Class C2, rated single/back to back capacitor bank breaking current 630/400 A

Rated voltages: 40.5kV.

Rated current up to 4000A.

2. Advanced embedding technology and solid-insulating process

Embedded poles: The three embedded poles of the VYG units totally enclose the vacuum interrupter, both upper and lower outgoing terminals cast in epoxy resin in APG process, a very mature automatic pressure gelatinizing technology. This helps to reduce adjustment requirements, diminish possible damage to the VI during assembly and protect connecting bolts against shock during operation. Also, discharge of the terminals can be prevented due to special conductive copper part. The embedded poles, in epoxy resin with unique material, make features of aging resistance, low/high-temperature resistance. These features protect the VI of the VYGQ system against any harmful influences from the outer environment. No shock & damp, pollution, condensation, dirt or small animal can ever have a possibility to face the VI, whereas those are always the headaches for the second generation. These distinctive features also enable the embedded poles a greater operating reliability, and high adaptability to various environments. The poles of the VYGQ series become truly maintenance-free.

Unique cushion bedding process: Since there is a great discrepancy of thermal expansion between the vacuum interrupter (which is enveloped with porcelain) and the epoxy resin (namely 1:10), that will certainly result in various troubles, for instance, cracking problems to the porcelain envelope or to the epoxy resin. However, the special VULCANIZE process is employed for VYGQ series to settle the above problems in this way: a special flexible bedding fills the spaces between the epoxy resin and the VI, creating a quality cushion that responds to all thermal expansions and contractions, protecting all applied material from any occurrence of aging or insulation degrading, and therefore ensuring the high reliability of the poles under various environmental conditions and the changes of them. This cushion also eliminates air gap between epoxy resin and VI, which may be ionized under high voltage electric field cause insulation or aging problem of embedded pole.

 