Remove Now
Cancle

ZN28A-12 12KV Indoor High-voltage Vacuum Circuit Breaker

ZN28(A)-12 series vacuum circuit breaker is an indoor high voltage switch with rated voltage 12KV, 3 phases AC 50 HZ . This product conforms to the standard GB1984-89 .

Description

  • Place of Origin: Zhejiang, China (Mainland)
  • Brand Name: hossin
  • Model Number: ZN28-12
  • Type: High Voltage
  • Poles Number: 3
  • Rated voltage: 12KV
  • Rated Current: 630A 1000A 1250A 1600A 2000A 2500A 3150A

ZN28(A)-12 series vacuum circuit breaker is an indoor high voltage switch with rated voltage 12KV, 3 phases AC 50 HZ .

This product conforms to the standard GB1984-89 .

There are two types of the main structure of circuit breaker: one is circuit breaker and operation mechanism  installed into one body. The other is circuit breaker and operation mechanism installed separately. The first one is the basic type of ZN28-12; The other type(split type) is applied for various fixed switchgear cabinets, such as GG-1A(Z) , XGN2-12(Z) etc.

This product can match in use with CD17,CD10A Model DC magnetic operating mechanism or CT17 and CT19 model spring energy storage operating mechanism. 

 

1. Altitude: ≤1000m;

2. Ambient temperature: -25°C ~+40°C ;

3. Relative humidity: daily average ≤95% , monthly average ≤90% ;

4. Earthquake intensity: 8 degree; 5. It should work in occasions without flammable and explosive matter, without corrosive chemical   and frequent severe vibration.

 

NO

                                                           item

 

 unit

specification

  20KA

  25KA

         31.5KA

           40KA

1

rated voltage

KV

 

12

 

 

2

higest working voltage

A

630.125

1250.16

1250.1600.2000.2500

1600.2500.3150

3

rated breaking current for short-circuit

KA

20

25

31.5

40

4

Rated short circuit switching current (peak)

KA

50

63

80

100

5

rated peak withstand current

KA

50

63

80

100

6

 rated withstand current for short-circuit in 4 mins

KA

20

25

31.5

40

7

rated insulated level

frequency withstand (before and after rated breaking and closing )

KV

42(48)

impact (before and after rated breaking and closing )

75(84)

8

rated operational

 

breaking -0.35-closing breaking 180s-closing breaking

9

lifetime

Times

10000

10

breaking times for rated current in short-circuit

Times

30

20

11

clearance between open contacts

mm

11±1

12

overtravel

mm

4±1

13

three phaseclosing and breaking

ms

≤2

14

Contact switching bounce time

ms

≤2

15

average breaking speed

m/s

1.2±0.3

16

average closing speed

m/s

0.6±0.2

17

time for breaking

under highest operational volatge

s

≤60

under lowest operational volatge

≤80

18

time for closing

s

≤100

19

Single-phase circuit resistance

u Ω

≤45

≤25

20

Static head accumulated allow wear thickness

mm

3

21

The oil buffer buffer stroke

 

 

     

 

ZN28A-12 12KV Indoor High-voltage Vacuum Circuit Breaker

Year Established:

Business Type:Manufacturer, Trading Company

Management Certifiation:

Operational Address: Niqian Village, Xiangyang Town, Yueqing, Wenzhou, Zhejiang, China (Mainland)