Remove Now
Cancle

Kyn44-12 Indoor Type AC Metal-Clad MID-Set Withdrawable Switchgear

KYN44-12 indoor type alternating-current metal-clad mid-set withdrawable switchgear is applicable for three-phase power systems of AC50Hz and 3.6~12kV, used for electric energy receiving and distribution. Certification: ISO9001; Installation: Fixed; Current: AC.

Description

  • Model NO.: KYN44-12
  • Shell Material: Steel Plate
  • Structure: Cabinet
  • Trademark: HONLE
  • Specification: Rated frequency: 50HZ
  • HS Code: 8504401990
  • Certification: ISO9001
  • Installation: Fixed
  • Current: AC
  • Transport Package: Standard Export Carton
  • Origin: Zhejiang, China (Mainland)

KYN44-12 indoor type alternating-current metal-clad mid-set withdrawable switchgear is applicable for three-phase power systems of AC50Hz and 3.6~12kV, used for electric energy receiving and distribution, is a PTD control device for single-bus segment systems. It is mainly used in power plants and substations for power transmission, and industrial and mining enterprises for power distribution, as well as secondary substations for power receiving and transmission and starting of large high-voltage motors, etc, realizes control, protection and monitoring.

 

1.Fully compatible with technical performances and schemes of KYN28A-12, GZS and other switchgears. 

2.More mechanical interlocking protection and operation characteristics. 

3.Complete mechanical interlocking protection and operation characteristics.

4.A variety of configurations of vacuum circuit breakers.  

5.w-vac vacuum circuit breaker from Westing House Corporation. 

6.VD4 vacuum circuit breaker from ABB Corporation. 

7.3AH5 vacuum circuit breaker from SIEMENS.

8.10-VPR vacuum circuit breaker from MITSUBISHI.

9.ZN28GE and VB2 vacuum circuit breakers from GE. 

10.EV12 vacuum circuit breaker from Merlin Gerin. 

11.VS1 vacuum circuit breaker from Senyuan Corporation. 

12.All kinds of homemade vacuum circuit breakers such as VS1, ZN28, ZN63, ZN, etc. 

Adoption of imported and homemade microcomputer-based monitor and remote controller, or electromechanical relay protection and meter monitoring. 

Luxurious imported type, universal type and economical type for option. 


Technical parameters

Outline dimension of switchgear (mm)

 Breaker model

 W-VAC 

 VPR

 3AH5

 VD4,VS1,ZN28,ZN63

Height (H)

 2300

 2300

 2300

 2300

Width (W)

 ≤1250A>1600-3150A

 700
       800

 800
       1000

 800
       1000

 800
       1000

Depth (D)

 1660 

 1660

 1600

1500 (Note 2)

Note: 1. Cabinet width is 800 except the breaker cabinet whose width varies.
2. Depth of incoming/outgoing cables is 1660.

 

Main technical parameters of switchgear 

Item

 Unit

Data

Rated voltage

 KV

 3.6,7.2,12

Rated insulation level

 1min power frequency withstand voltage
Lightning impulse voltage (full wave)

 KV
       KV

 24,32,42
       40,60,75

Rated frequency
Rated current 
Rated current of main bus
Rated current of branch bus
4s short-time withstand current (effective value)
Rated peak withstand current (peak)

 Hz
 A
  A 
  A 
   KA 
  KA

 

 50
       5-3150
       1600,2000,2500,3150 
       630,1250,1600,2000,2500,3150 
       16,20,25,31.5,40,50 
       40,50,63,80,100,125

 Protection class

 

 The shell is IP4X, and it is IP2X when the circuit breaker chamber door is opened

Note: please take the breaker model into consideration especially for short-circuit capacity of current transformer. 

 Corporation

 C-H

 ABB

 SIEMENS

GE

Mitsubishi

Homemade

 Model 

 W-VAC

 Vd4

 3AH5

 ZN28GE,VB2

 VPR

 VS1,ZN28,ZN63…

 

Kyn44-12 Indoor Type AC Metal-Clad MID-Set Withdrawable Switchgear

Year Established:

Business Type:Manufacturer, Trading Company

Management Certifiation:

Operational Address: Xiangyang Industrial Zone, Liushi Town, Yueqing, Wenzhou, Zhejiang, China