Remove Now
Cancle

Low-noise fans for transformer

The low noise fan for transformer has several characteristics such as the light weight, stable performance and low noise etc. the protecting grade of this low noise fan is IP55 and its fan structure is: straight axis link by the axis flowing type impeller with the outdoor three different phase electromotor.Email: yuyang@mec.com.cn

Description

Email: yuyang@mec.com.cn
 
Product
The low noise fan fory transformer is developed. Designed and manufacture together with Zhejiang university hydrokinetics graduates school according to the mechanical sector standard JB/T96421999 《Transformer Fan》. The low noise fan used by transformer is specially used on the big and middle-sized transformer cooler and radiator. The vane of this low noise fan adopts the aerofoil type and its material adopts the die-casting aluminum. Compared with the same type steeliness products. The low noise fan used transformer has several characteristics such as the light weight, stable performance and low noise etc. the protecting grade of this low noise fan is IP55 and its fan structure is: straight axis link by the axis flowing type impeller with the outdoor three different phase electromotor.

Special environment code
W-denoted general outside condition and can be ignored
TH-denoted humid tropic
TA-denoted dry tropic

Direction of wind
Q-front (air from the motor to the impeller)
H-back (air from the impeller to the motor)
Note: Give indication of the product specification and type while you order it.

Performance parameter

model

mm

M³/h

Pa

r.p.m

kw

v

Hz

A

db(A)

4Q-4

Ø400

4200

103

1440

0.25

380

50

0.8

68

5Q-4

Ø500

5600

144

1440

0.55

380

50

1.6

70

5Q-6

Ø500

7200

120

960

0.37

380

50

1.2

62

5Q-8

Ø500

5800

70

720

0.25

380

50

1.1

58

5Q-10

Ø500

4700

50

580

0.18

380

50

1.1

57

6Q-8

Ø600

8590

100

720

0.37

380

50

1.5

64

6.3Q-6

Ø630

10600

130

960

0.55

380

50

1.9

66

6.3Q-8

Ø630

9000

100

720

0.37

380

50

1.4

62

7Q-6

Ø700

14600

150

960

0.75

380

50

2.2

73

7Q-8

Ø700

13500

130

720

0.55

380

50

2.2

64

7Q-10

Ø700

11100

65

580

0.25

380

50

1.2

58

7Q-12

Ø700

9500

50

480

0.18

380

50

1.1

55

7.3Q-8

Ø730

14500

130

720

0.55

380

50

1.9

66

7.3Q-10

Ø730

11800

75

580

0.37

380

50

1.5

58

73.Q-12

Ø730

10000

60

480

0.25

380

50

1.3

54

8Q-6

Ø800

16000

216

960

1.50

380

50

4.0

75

8Q-8a

Ø800

19200

90

720

0.55

380

50

2.2

65

8Q-8b

Ø800

16000

135

720

0.75

380

50

2.4

68

8Q-10

Ø800

14500

70

580

0.37

380

50

1.5

64

8Q-12

Ø800

13500

55

480

0.25

380

50

1.3

57

9Q-6

Ø900

18000

165

960

1.50

380

50

4.0

73

9Q-8

Ø900

16000

150

720

1.10

380

50

3.0

68

9Q-10

Ø900

18000

90

580

0.75

380

50

3.2

64

9Q-12

Ø900

16000

70

480

0.55

380

50

2.3

60

9Q-14

Ø900

13500

65

400

0.37

380

50

1.9

57

10Q-8

Ø1000

25000

185

720

2.20

380

50

5.8

71

10Q-10

Ø1000

22000

135

580

1.10

380

50

3.2

67

10Q-12

Ø1000

19000

100

480

0.75

380

50

1.9

65

10Q-14

Ø1000

17000

80

400

0.37

380

50

1.9

60

10Q-16

Ø1000

15000

70

360

0.37

380

50

3.0

55

11Q-12

Ø1100

21000

80

480

0.75

380

50

3.1

64

11Q-16

Ø1100

19000

68

360

0.55

380

50

3.5

60

12.5Q-16

Ø1250

25000

60

360

0.75

380

50

 

65

Operation conditions
The ambient air temperature :between -40℃ and 75℃
Height above sea level: less than 1000m
The relative humidity: the highest average relative humidity in the most moist month is 95% with the lowest average temperature
The maximum sun radiation intensity: 0.98kw/㎡
The maximum rainfall intensity: 50mm/10min
Allow the sand and dust existing, ice, frost and dew existing
Motor use IP55 protection class and fclass insulation ,when altitude is less than 1000m and round air temperature (measure with thermometer)less than 75℃,the temperature of resistor winding is not excess 45K and the allowable temperature(measure with thermometer) of the bearing not excess 95℃
The motor uses low-noise bearing. It can continuous run in the rated load under the normal using conditions.

Year Established:

Business Type:

Management Certifiation:

Operational Address: