Low-noise fans for transformer
The low noise fan for transformer has several characteristics such as the light weight, stable performance and low noise etc. the protecting grade of this low noise fan is IP55 and its fan structure is: straight axis link by the axis flowing type impeller with the outdoor three different phase electromotor.Email: yuyang@mec.com.cn
Description
Email: yuyang@mec.com.cn
Product
The low noise fan fory transformer is developed. Designed and manufacture together with Zhejiang university hydrokinetics graduates school according to the mechanical sector standard JB/T96421999 《Transformer Fan》. The low noise fan used by transformer is specially used on the big and middle-sized transformer cooler and radiator. The vane of this low noise fan adopts the aerofoil type and its material adopts the die-casting aluminum. Compared with the same type steeliness products. The low noise fan used transformer has several characteristics such as the light weight, stable performance and low noise etc. the protecting grade of this low noise fan is IP55 and its fan structure is: straight axis link by the axis flowing type impeller with the outdoor three different phase electromotor.
Special environment code
W-denoted general outside condition and can be ignored
TH-denoted humid tropic
TA-denoted dry tropic
Direction of wind
Q-front (air from the motor to the impeller)
H-back (air from the impeller to the motor)
Note: Give indication of the product specification and type while you order it.
Performance parameter
model
|
mm
|
M³/h
|
Pa
|
r.p.m
|
kw
|
v
|
Hz
|
A
|
db(A)
|
4Q-4
|
Ø400
|
4200
|
103
|
1440
|
0.25
|
380
|
50
|
0.8
|
68
|
5Q-4
|
Ø500
|
5600
|
144
|
1440
|
0.55
|
380
|
50
|
1.6
|
70
|
5Q-6
|
Ø500
|
7200
|
120
|
960
|
0.37
|
380
|
50
|
1.2
|
62
|
5Q-8
|
Ø500
|
5800
|
70
|
720
|
0.25
|
380
|
50
|
1.1
|
58
|
5Q-10
|
Ø500
|
4700
|
50
|
580
|
0.18
|
380
|
50
|
1.1
|
57
|
6Q-8
|
Ø600
|
8590
|
100
|
720
|
0.37
|
380
|
50
|
1.5
|
64
|
6.3Q-6
|
Ø630
|
10600
|
130
|
960
|
0.55
|
380
|
50
|
1.9
|
66
|
6.3Q-8
|
Ø630
|
9000
|
100
|
720
|
0.37
|
380
|
50
|
1.4
|
62
|
7Q-6
|
Ø700
|
14600
|
150
|
960
|
0.75
|
380
|
50
|
2.2
|
73
|
7Q-8
|
Ø700
|
13500
|
130
|
720
|
0.55
|
380
|
50
|
2.2
|
64
|
7Q-10
|
Ø700
|
11100
|
65
|
580
|
0.25
|
380
|
50
|
1.2
|
58
|
7Q-12
|
Ø700
|
9500
|
50
|
480
|
0.18
|
380
|
50
|
1.1
|
55
|
7.3Q-8
|
Ø730
|
14500
|
130
|
720
|
0.55
|
380
|
50
|
1.9
|
66
|
7.3Q-10
|
Ø730
|
11800
|
75
|
580
|
0.37
|
380
|
50
|
1.5
|
58
|
73.Q-12
|
Ø730
|
10000
|
60
|
480
|
0.25
|
380
|
50
|
1.3
|
54
|
8Q-6
|
Ø800
|
16000
|
216
|
960
|
1.50
|
380
|
50
|
4.0
|
75
|
8Q-8a
|
Ø800
|
19200
|
90
|
720
|
0.55
|
380
|
50
|
2.2
|
65
|
8Q-8b
|
Ø800
|
16000
|
135
|
720
|
0.75
|
380
|
50
|
2.4
|
68
|
8Q-10
|
Ø800
|
14500
|
70
|
580
|
0.37
|
380
|
50
|
1.5
|
64
|
8Q-12
|
Ø800
|
13500
|
55
|
480
|
0.25
|
380
|
50
|
1.3
|
57
|
9Q-6
|
Ø900
|
18000
|
165
|
960
|
1.50
|
380
|
50
|
4.0
|
73
|
9Q-8
|
Ø900
|
16000
|
150
|
720
|
1.10
|
380
|
50
|
3.0
|
68
|
9Q-10
|
Ø900
|
18000
|
90
|
580
|
0.75
|
380
|
50
|
3.2
|
64
|
9Q-12
|
Ø900
|
16000
|
70
|
480
|
0.55
|
380
|
50
|
2.3
|
60
|
9Q-14
|
Ø900
|
13500
|
65
|
400
|
0.37
|
380
|
50
|
1.9
|
57
|
10Q-8
|
Ø1000
|
25000
|
185
|
720
|
2.20
|
380
|
50
|
5.8
|
71
|
10Q-10
|
Ø1000
|
22000
|
135
|
580
|
1.10
|
380
|
50
|
3.2
|
67
|
10Q-12
|
Ø1000
|
19000
|
100
|
480
|
0.75
|
380
|
50
|
1.9
|
65
|
10Q-14
|
Ø1000
|
17000
|
80
|
400
|
0.37
|
380
|
50
|
1.9
|
60
|
10Q-16
|
Ø1000
|
15000
|
70
|
360
|
0.37
|
380
|
50
|
3.0
|
55
|
11Q-12
|
Ø1100
|
21000
|
80
|
480
|
0.75
|
380
|
50
|
3.1
|
64
|
11Q-16
|
Ø1100
|
19000
|
68
|
360
|
0.55
|
380
|
50
|
3.5
|
60
|
12.5Q-16
|
Ø1250
|
25000
|
60
|
360
|
0.75
|
380
|
50
|
|
65
|
Operation conditions
The ambient air temperature :between -40℃ and 75℃
Height above sea level: less than 1000m
The relative humidity: the highest average relative humidity in the most moist month is 95% with the lowest average temperature
The maximum sun radiation intensity: 0.98kw/㎡
The maximum rainfall intensity: 50mm/10min
Allow the sand and dust existing, ice, frost and dew existing
Motor use IP55 protection class and fclass insulation ,when altitude is less than 1000m and round air temperature (measure with thermometer)less than 75℃,the temperature of resistor winding is not excess 45K and the allowable temperature(measure with thermometer) of the bearing not excess 95℃
The motor uses low-noise bearing. It can continuous run in the rated load under the normal using conditions.

Year Established:
Business Type:
Management Certifiation:
Operational Address:
Verified Supplier
Credit Check
More from this Supplier