Oil flow relay

The oil flow indicator is used for showing the quantity of oil flow in the transformer cooling system with forced oil circulation and supervising the operation situation of oil pump of cooling system with forced oil circulation, such as whether the rotation direction of oil pump is correct, the valve is opened, the conduit is blocked, ect, The indicator can initiate the alarming signal when the quantity of oil flow increase to the action oil quantity or decrease to the return oil flow quantity. The product is improved by technician absorb the suggestion with asked to improved and perfect the Oil Flow Relay which used by Power Station, Substation. We adopted the advanced technique of abroad afresh improved the design. At present the goods is most advanced and perfect in abroad. Email: yuyang@mec.com.cn

Description

Email: yuyang@mec.com.cn
 
The character of product
The point of the item adopted the quakeproof construction
The active stalk and passive stalks propelled by bearing, the action is vivid. Its impossible to choke that the organization which arouse to point is choded.
The point of minature switch produced by movable plate, and the dependable is high.
The lengthes of propelled bearing and the connecting pipe is equed,that enhanced the stalk′s strength

Operation Conditions
The temperature of ambient :-30°C- +40°C;
Relative humidity: When the air temperature is +25°C,the relative humidity shall not exceed 90%;
The oil temperature not exceed 90°C;
The installation place around which any violent vibration and jolt are not exist;
The parameter (i.e. the action character) of oil flow quantity of indicate shall be in accordance with that of the transformer cooling system.

Main technical parameter
 The main specification and technical parameters of indicator are shown in table1

 

Type

Normal Dia. Of connecting mm

Rated working quantity of flow m³/h

Action oil flow quantity

Return oil flow quantity

Rates of contact

YJ1-50/20

50

20

15±10%

11±10%

 

 

 

交流

AC

 

380V 3A

 

220V 5A

YJ1-80/40

80

40

30±10%

22±10%

YJ1-80/45

80

45

30±10%

18±10%

YJ1-100/60

100

60

30±10%

20±10%

YJ1-100/80

100

80

60±10%

40±10%

YJ1-100/90

125

90

68±10%

50±10%

YJ1-125/80

125

80

60±10%

40±10%

YJ1-125/150

150

150

100±10%

75±10%

YJ1-150/40

150

40

30±10%

22±10%

YJ1-150/60

150

60

45±10%

30±10%

YJ-150/80

150

80

60±10%

44±10%

YJ-150/120

150

120

90±10%

60±10%

YJ-150/125

150

125

94±10%

63±10%

YJ-150/135

150

135

101±10%

75±10%

YJ-150/145

150

145

108±10%

72±10%

NoteFor the technical parameter of special ordering product, please according to its certificate.



Working principle of Indicator oil flow
After the oil pump of transformer cooling system starts, the oil flow will circulate. When the quantity of oil flow increase to the action oil flow     quantity, the movable plate of the Indicator oil flow will be pushed to rotate to the limit position, the Indication part will rotate synchronously, the point will turn to corresponding position ,the normal open contact of micro operation switch will close, normal operation signal will be initiated. When the quantity of oil flow decreases to the return oil flow quantity (or does not reaches to the action oil flow quantity), the movable plate will return to the original position by means of the action of the spring, and the normal open contact of the micro operation switch will open and the normal close contact will close, the fault signal will be initiated.
 