Remove Now
Cancle

Oil-immersed electrical reactor

 relative developed software are adopted in Electromagnetic calculations, strength analysis, leakage magnetic distribution, its electro-dynamic force and electrical insulation.
 
Please contact us! Email: yuyang@mec.com.cn
 

Description

 

 

Email: yuyang@mec.com.cn

Skype:snowing1203
MSN:luckywang03@hotmail.com

 

 

Features:

Design: relative developed software are adopted in Electromagnetic calculations, strength analysis, leakage magnetic distribution, its electro-dynamic force and electrical insulation.

Manufacture:

Core: effectively upgrade transformer’s no-load performance by below methods:

1)    The core is made of high-permeable grain-orientated top quality cold-rolled silicon sheet and the material is cut with advanced Germany Geoge GmbH automatic shear line with the cut burs controlled within 0.02mm.

2)    The silicon sheet fabrication adopts “no-upper yoke lapped’ technology and all lapped joints of the silicon sheet are 45 full-miters. The laminated core sheets are integrally pressed and adhered with epoxy resin to make the three –leg two-yoke core a strong and flat integral one with good verticality precision, this effectively improves no-load performance and reduces noises.

3)    Bracing plates are used as support between coil leg and inner coil. The iron yoke is tied with epoxy resin-impregnated glass fiber band, and the lower section of oil tank is tightened with counter-pressure bolts. The upper iron and the upper section of oil tank are fixed at three locations. Hence the body inside the oil tank can withstand the vibration during transportation without any shift.

 Winding:

1)    The high-voltage (HV) coil adopts an interleaved-continuous structure to improve the voltage characteristics under impact voltage and make voltage evenly distributed. All stays and pads are chamfered to keep highly reliable insulation.

2)    In the transformer winding there is a zigzag oil guide structure so as to fully cool all areas inside the winding, lower the temperature rise of the winding and the hot points of the winding and prolong the service life of insulation. The HV and MV regulation system are independently provided with voltage-regulating winding to balance the ampere turn of each winding,  effectively lower the axial electrodynamic force generated at short-circuit of transformer and improve abrupt short-circuit withstanding capacity.

3)    The winding adopts radial “0” margin designed, between the core and the paper sleeve of LV winding, and between the LV, HV, voltage-regulating windings, as well as before insertion of stays and shroud plate they are fully dried and tightly matched to ensure extremely good compactness and concentricity of the entire winding.

Oil tank and accessories

1)  The tank wall adopts wide steel sheet, which will be folded into corrugated structure without splicing, in this way welds are decreased and mechanical strength is enhanced, meanwhile, the corrugated wall has diverging effect, and thus plays a role in decrease of noise. The routing troughs and control cabinets of the secondary circuit are all made of stainless steel, so the entire transformer has a simple and good looking.

2)  All sealing surface use quality sealing material and are precision-machined.

3)  On the edge of the tank there are double sealing grooves, and the outer sealing material is used to shade the atmosphere and ultra-ray to protect the inner sealing being damaged, thus at utmost prolonging service life and enhancing reliability of the seal.

Model

Condenser Multiple technical parameter

Rated capacity

Rated voltage

Rated inductance

Loss

Dimension

Weight

Rated capacity

Rated voltage

KVAR

KV

KVAR

KV

mH

KW

L

B

H

I

b

φ

Kg

CKS-36/10-6

600

10

36

0.381

31.5

0.65

1300

930

910

500

500

14

420

KKS-56/10-6

933

10

56

0.381

49

0.90

1360

960

1000

480

550

14

560

CKS-72/10-6

1200

10

72

0.381

63

1.08

1360

960

1130

480

550

14

720

CKS-200/10-6

3333

10

200

0.381

175

2.34

1500

1200

1250

600

650

18

1200

CKS-100/10-12

833

10

100

0.381

40.1

1.40

1400

1000

1100

500

500

18

900

CKS-300/10-12

2500

10

300

0.381

120.3

3.17

1500

1100

1350

600

650

20

1700

CKS-600/10-12

5000

10

600

0.381

240.7

5.33

1650

1000

1760

660

660

20

2350

CKS-960/10-12

8000

10

960

0.381

385

7.58

1900

1200

1800

900

980

20

3150

CKS-216/35-6

3600

35

216

1.32

54.55

2.82

1860

1000

1880

820

660

20

1620

CKS-540/35-6

9000

35

540

1.32

136.4

5.60

2000

1080

2000

900

750

20

2100

CKS-720/35-6

12000

35

720

1.32

181.8

6.95

2100

1100

2100

900

750

24

3400

CKS-960/35-6

16000

35

960

1.32

242.4

8.60

2300

1200

2200

980

980

24

4600

CKS-340/35-12

2000

35

240

2.88

27.78

3.05

2100

1080

2000

900

750

20

1900

CKS-540/35-12

4500

35

540

2.88

62.5

5.60

2200

1100

2000

900

750

20

2300

CKS-720/35-12

6000

35

720

2.88

83.3

6.95

2200

1100

2100

900

750

24

3500

CKS-960/35-12

8000

35

960

2.88

111.1

8.62

2300

1200

2100

980

980

24

4800

CKS-1200/35-12

10000

35

1200

2.88

138.9

10.20

2500

1300

2200

1100

1000

24

6200