Remove Now
Cancle

XGN-12 SF6 Metal-Clad Enclosed Ring Main Unit Switchgear

The Ambient temperature upper limit and lower limit are respectively +40°C and -40°C; (allowing storage and transportation at -30°C);

Description

  • Place of Origin: Zhejiang, China (Mainland)
  • Brand Name: LIYOND
  • Model Number: XGN-12
  • SWITCHGEAR Standard: IEC
  • SWITCHGEAR Rated voltage: 12/24/40.5kv
  • SWITCHGEAR Rated current: 630A,1250A
  • Breaking current: 31.5KA
  • Frequency: 50Hz or 60Hz

 

Product Overview :

XGN-12 switchboard is suitable for single busbar systems with power levels of 10KV three-phase AC 50Hz to accept and distribute power. The switchboard is new generation small power equipment used in cities and rural areas. which is distinguished with features as small volume, low cost, safety and dependability, simple in running and operation, and accommodates to the demand of power market, reform of city and rural power grids, and packaged substaions. 

Working Conditions:
a. The Ambient temperature upper limit and lower limit are respectively +40°C and -40°C; (allowing storage and transportation at -30°C);
b. Altitude is not more than 1000m;
c. Relative humidity: daily average value should not be more than 95%, while monthly average value should not be more than 90% (+25°C);
d. Seismic intensity should be not more than 8°;
e. Places without fire, explosion risk, serious pollution, chemical corrosion and violent vibration.

 

Advantages:

This switchgear is case metal-enclosed structure. In accordance with the national standard GB3906 and international standardIEC298, protection degreeIP2X. The metal-enclosed structure effectively prevents short-circuit failure by intruders .

When air insulation distance between polar to polar or polar to ground ≤125mm, porcelain support insulators (≥8000N) is applied. All these ensure higher insulation intensity and stability.

Breakers, both upper and lower insulation switches, grounding switches and interlock mechanisms between doors all takes force mechanical lock mode to meet the requirement of "five- prevention".

 

Technical parameters :

No.

Name

Unit

Data

1

Rated Voltage

KV

3,6,10

2

Rated Current

A

630,1000,1250,1600,

2000,2500,3150

3

Rated Frequency

Hz

50

4

Rated short-circuit current(valid value)

kA

20, 25

31.5

40

5

Rated ripe stable current (peak value)

kA

20, 25

31.5

40

6

Rated dynamic stable current(peak value)

kA

40

80

100

7

Rated power frequency tolerant voltage

Inter-polar /polar to ground

kV

42

Inter-fracture

kV

48

8

Rated lightening shock tolerance voltage

Inter-polar /polar to ground

kV

75

Inter-fracture

kV

85

9

Rated thermal time

s

4

10

Protection degree

 

1P2X

11

Outline dimensions

       

XGN-12 SF6 Metal-Clad Enclosed Ring Main Unit Switchgear