Remove Now
Cancle

YB20 Prefabricated Substation

Product Structure Features
good corrosion,waterproof and dust resistance,
beautiful appearance,
easy to transport and mainte

Description

Instruction

Altitude: below1000m; (Up to 4000m offering available upon request. Please contact manufacturer for more information).

 Ambient Temperature:-30~+40

 Temperature: Max monthly average temperature below +30. Max  annual average temperature below +20;

Relative Humidity: Max daily average relative humidity bwlow 95%, max monthly average relative humidity below 90%;

Seismic design:  horizontal acceleration below 0.4m/s2, vertical acceleration below 0.15 m/s2

Installation Site: no severe collision, no serious pollution and chemical corrosion, no conductive dust and explosion danger;

 When cannot meet the requirement of the normal use conditions, please negotiate with our company.

 

 

YB20  Prefabricated Substation

 

[performance parameter]

 

project

unit

parameter

MV unit

Rated frequency

HZ

50

Rated voltage

KV

6

10

35

maximum working voltage

KV

6.9

11.5

40.5

Rated current

A

400,630,1250

Transfer current

A

1200~3150

power frequency withstand voltage   over the ground and phase to phase/break

KV

42/48

Lighting impulse withstand voltage   over the ground and phase to phase/break

KV

75/85

Rated  short -circuit breaking current(current limiting fuse)

KA

31.5

Transformer unit

Rated voltage

KV

6,10,35

Rated capacity

KVA

30-2000

Tapping range

%

±2×2.5%,±5%

Vector groups

 

Yyno,Dyn11

Uk%

%

4,4.5,6,8

LV unit

Rated voltage

V

220,380,690,1000

rated current of main circuit

A

50-4000

branch current

A

5-800

enclosure

Protection class

 

MV compartment; transformer compartment; LV

compartment

 

noise level

Db

below 50

 