Main parameters of 10kV vacuum load switch and combination electric appliance

#

Parameter name

unit

 

 

Combination electric appliance

1

Rated voltage

KV

12

12

12

2

Rated frequency

Hz

50

50

50

3

Rated current

A

630

200

200

4

Rated short time withstand current(4S)

KA

20

 

 

5

Rated peak value withstand current (peak )

KA

50

 

 

6

Rated short circuit making current(peak)

KA

50

 

 

7

Rated short circuit breaking current

KA

 

31.5

 

8

Take-over current

A

 

3150

 

9

1min power frequency withstand voltage,interphase and grounding/fracture

KV

42/49

42/49

42/49

10

Lightning impulse withstand voltage(peak)interphase and grounding/fracture

KV

75/85

75/85

75/85

11

Mechanical life

Times

10000

1000

10000

 

 

Main parameters of 35kV combination electric appliance

No.

Parameters` name

unit

Combination electric appliance

1

Rated voltage

KV

40.5

2

Rated current

A

50.63

3

Rated frequency

Hz

50

4

Rated short circuit breaking current

KA

20

5

Rated take-over current

A

1200

6

Rated short time power frequency withstand voltage

KV

95

7

Lightning impulse withstand voltage

KV

185

8

Rated short time power frequency withstand voltage(isolated fracture)

KV

115

9

Lightning impulse withstand voltage(isolated fracture)

KV

215

10

Mechanical life

Times

10000

Main parameters of vacuum circuit breaker

No.

Parameters name

unit

ZN12-HC

ZN-40.5-HC

1

Rated voltage

KV

12

40.5

2

Rated frequency

Hz

50

50

3

Rated current

A

630,1250

1250,1600

4

Rated short time withstand current(4S)

KA

25,31.5

25,31.5

5

Rated peak value withstand current (peak )

KA

63,80

63,80

6

Rated short circuit breaking current

KA

25,31.5

25,31.5

7

Rated short circuit making current(peak)

KA

63,80

63.80

8

1min power frequency withstand voltage,interphase and grounding/fracture

KV

42/48

95/115

9

Lightning impulse withstand voltage(peak)interphase and grounding/fracture

KV

75/85

185,/215

10

the times of rated short circuit breaking

Times

50

30

 