ZW6-12 Series 12KV 3 phase High voltage vacuum circuit breaker
ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker is used for rated voltage 12KV and below, three phases, AC50Hz, power system, to switch on/off loading current, over-current, and short circuit in rural or urban power network, and for similar application, also for sectionalizer of urban 12KV network.
Description
- Place of Origin: Zhejiang, China (Mainland)
- Brand Name: AISO/OEM
- Model Number: ZW6-12
- Type: Vacuum, Indoor
- Poles Number: 3
- Product: ZW6-12 Circuit Breaker
- Rated Voltage: 12KV
- Rated current: 630A
- Rated frequency: 50Hz
- Mechanical life: 10000Times
- Uses: High voltage
- Standard: IEC
- Customized: Accept special order
- Port: Ningbo/Shanghai
General Description
ZW6-12/630-16(20) Series outdoor high voltage vacuum circuit breaker is used for rated voltage 12KV and below, three phases, AC50Hz, power system, to switch on/off loading current, over-current, and short circuit in rural or urban power network, and for similar application, also for sectionalizer of urban 12KV network.
Main Technical Parameters
Technical parameters of breaker as sheet 1
|
Item
|
Description
|
Unit
|
Data
|
|
1
|
Rated voltage
|
KV
|
12
|
|
2
|
Rated insulation level
|
1min withstand voltage
|
Dry
|
42
|
|
Wet
|
34
|
|
Lightning impulse withstand voltage(peak)
|
75
|
|
3
|
Rated current
|
A
|
630
|
|
4
|
Rated frequency
|
Hz
|
50
|
|
5
|
Rated short circuit breaking current
|
KA
|
12.5 16 20
|
|
6
|
Rated short circuit making current(peak)
|
31.5 40 50
|
|
7
|
Rated peak withstand current
|
31.5 40 50
|
|
8
|
Rated short time withstand current
|
12.5 16 20
|
|
9
|
Operating sequence
|
|
OC-0.3s-CO-180S-CO
|
|
10
|
Nos of breaking rated short circuit breaking current
|
Times
|
30
|
|
11
|
Mechanical life
|
10,000
|
|
12
|
Rated operating voltage CT spring operating mechanism provided
|
|
DC24,48V,AV DC110V,220V
|
|
13
|
Permissible abraded thickness of contact
|
mm
|
3
|
|
14
|
Rated current of over-current release
|
A
|
5
|
|
15
|
Weight
|
kg
|
130
|
Note:Please contact the factory to confirm the latest parameters
Breaker assembly and physical parameters as sheet 2
|
Item
|
Description
|
Unit
|
Data
|
|
1
|
Opening distance of contact
|
mm
|
9±1
|
|
2
|
Over travelling distance of contact
|
3±1
|
|
3
|
Average closing speed
|
s
|
1.0±0,2
|
|
4
|
Average opening speed
|
0.6±0.2
|
|
5
|
Jumping time of contact at closing
|
ms
|
≤2
|
|
6
|
Asychrony of three phase opening
|
|
7
|
Closing time
|
s
|
≤0.1
|
|
8
|
Opening time
|
Highest operating voltage
|
≤0.06
|
|
Lowest operating voltage
|
≤0.1
|
|
9
|
DC resistance of each phase circuit
|
μΩ
|
≤200
|
|
10
|
Central distance between phase(in arc extinguishing chamber)
|
mm
|
193
|