Remove Now
Cancle

zw32-12-001 50HZ Middle Voltage Vacuum Circuit Breakers

1.Founded in 2002, registered capital is 30.1 million RMB; 2.Company covers 100000 square meters, more than 300 staffs;

Description

  • Place of Origin: Henan, China (Mainland)
  • Brand Name: Runner
  • Model Number: zw32-12-001
  • Type: Vacuum
  • Poles Number: 3
  • circuit breakers types: spring and permanent magnet
  • circuit breakers voltage: 12KV
  • circuit breakers current: 630A 1250A
  • circuit breakers rated frenquency: 50HZ
  • vacuum circuit breakers opening speed: 1.2±0.2ms
  • circuit breakers closing speed: 0.6±0.2ms
  • middle voltage circuit breakers weight: 120kg
  • circuit breakers altitude: less than 1000m
  • circuit breakers working temperature: - 40℃-- 50℃

 

Middle Voltage Vacuum Circuit Breakers

1.Founded in 2002, registered capital is 30.1 million RMB;

2.Company covers 100000 square meters, more than 300 staffs;

3.Professional R&D team, and 5 advanced production lines, annual sales value 120 millions .

4.We have another 2 subcompanies, offices across the country, wonderful agent sales network;

5.Products are exported to more than 20 countries around the world.

 

Middle Voltage Vacuum Circuit Breakers Advantage:

Vacuum circuit breakers insulation test: Main electricity loop insulation is stable and reliable;

Circuit breakers  Mechanical property and environmental testing: mechanical property is stable and reliable;

Vacuum circuit breakers Temperature rise test: Vacuum interrupter with ultra-low resistance, contacting resistance is low;

Middle voltage circuit breakersTesting for Turning on or off and opening or closing on rated short circuit :

Circuit breakers High vacuum breaking ability is great, insulation recovery is fast, breaker finished short-circuit current test for 30 times;

Circuit breakers Testing for short-time withstand current and peak withstand current:

Vacuum circuit breakers test for 4 seconds withstand current and short-time peak withstand current, power receiving ability on main loop is great;

Testing for life : 30000 times finished on State new standard M2 grade.

Middle Voltage Vacuum Circuit Breakers Manufacturing Standards:

 

IEC62271-100-2006

IEC62271-1

GB1984-2003

GB/T11022-1999

DL/T402-2007

DL-T593-2006

JB/T3855-2008

 

Middle Voltage Vacuum Circuit Breakers Technical Parameters:

 

No

Items

Unit

Number

1

Rated voltage

KV

12

2

Rated current

A

630 or 1250

3

Rated frequency

Hz

50

4

Power frequency resisting voltage(1min)

KV

42

5

Withstand current(peak) for thunder

KV

75

6

Rated short-circuit current for turning on or off

KA

16/20/25

7

Rated short-circuit current for opening or closing (peak number)

KA

50

8

Rated peak withstand current

KA

50

9

4s short-time withstand current

KA

20

10

Rated operation cycle

 

s-0.1s-ms-6s-ms-6sms-60s recovery

11

Number of times for rated short-circuit current on or off

times

30

12

Life

times

30000

13

Permanent-magnet device control voltage

V

DC 220

 zw32-12-001 50HZ Middle Voltage Vacuum Circuit Breakers

Year Established:

Business Type:Manufacturer, Trading Company

Management Certifiation:

Operational Address: Floor 3-4, Bldg. 2, No. 101, Yulan Street, High-Tech Zone, Zhengzhou, Henan, China (Mainland)