Remove Now
Cancle

KYN28A-12 Single busbar Metal Clad High Voltage Switchgear

The cubicle is made of the imported alloy-coated steel sheet, and processed by the CNC machining and the multiple folding technology, and then assembled by the rivets and the high-strengthen bolts. With the application of the electrostatic spraying technology, the door has great impact and corrosion resistance capability, and high mechanical strength and elegant appearance.

Description

  • Place of Origin: Hunan, China (Mainland)
  • Brand Name: HNAC
  • Model Number: KYN28A-12
  • Name: High Voltage Switchgear Switchgear panel Switchboard
  • Main cabinet type: KYN28/KYN61/GGD/XGN15/...
  • Frequency: 50 HZ/60HZ
  • Design: Customized
  • Seismic intensity: not more than 8°C
  • Protection degree: IP4X for enclosure; IP2X for doors of compartments & circuit chambers
  • Main voltage range: 35KV/24KV/12KV/11KV/0.4KV
  • Certificate: ISO9001
  • Rated current: 630, 1250, 1600, 2000, 2500, 3150
  • Busbar system: Single busbar, and single busbar segments

 

Structural Features

 

1,The cubicle is made of the  imported alloy-coated steel sheet, and processed by the  CNC machining and the multiple folding technology, and then assembled by the rivets  and the high-strengthen bolts.  With the application  of the electrostatic  spraying technology, the door has great  impact and corrosion resistance  capability, and high mechanical  strength and elegant appearance. The main circuit breaker can select VS1 vacuum circuit breaker, ABB VD4 series devices and Schneider devices;

2,The handcart of the same type can be interchangeable reliably;

3,It is  provided with the  reliable and  simple mechanical interlocking  between the  circuit breaker and the disconnector, fully meeting the requirement of Fail Safe;

4,There has sufficient  linking and maintenance room  in the cable chamber.  The height of the cable linking  is around 800mm which  is high enough to  connect several cables  and easy for the maintenance;

5,The cubicle  is divided  into four independent  chambers, supporting  overhead incoming and outgoing  lines, incoming  and outgoing cables  and other  functional schemes. After the permutation and the combination, it can form various power distribution devices.

 

Ambient conditions

1, For the normal design, the  altitude should be not more than 1,000m. If  above 1,000m, it will design  according to the  altitude correction factor  of the  highland and manufacture as per the requirements suitable for the highland altitude.

2, The ambient  air temperature  ranges -35℃~+40℃, and  the average  temperature within 24h ≤ +35℃. If  exceeding the specified time, it  has to reduce the capacity  according to the actual condition;

3, The relative  humidity  should not  exceed 50%  at +40℃,  while  at lower  temperatures, larger  relative humidity  is acceptable,  e.g.  90% at  +20℃.  Considering the  change  of temperature may sometime cause the condensation, the daily average should be less than 95% and the monthly average less than 90%;

4, The  water  vapour   average  should  be ave2.2*10-3Mpa  or  below   while  the  monthlyrage not larger than  1.8*10-3Mpa;

5, The gradient between installation surface and vertical plane is ≤ 5°;

6, The seismic intensity should be not more than 8 degree;

7, Frequent severe violation is acceptable;

8, No pollution is  allowed to the ambient  air, such as corrosive  substance, flammable gas, vapour and so on.

 

 

Technical parameters

No.

Description

Unit

Technical Parameter

1

Rated voltage

KV

3,6,10

2

Peak work voltage

KV

3.6,7.2,12

3

Rated frequency

Hz

50(60)

4

Rated current

 

 Rated short breaking current

A

 

KA

630, 1250, 1600, 2000, 2500, 3150  

 

    16, 20, 25, 31.5, 40

 

5

4S thermal steady current

(effective value)

KA

16, 20, 25, 31.5, 40

6

Rated dynamic steady current

(peak)

KA

40, 50, 63, 80, 100

7

1min rated power

 

frequency withstand voltage

 

KA

Fracture: 42

KV

Inter-polar: 48

8

Lightning impulse withstand voltage

KV

75/85

9

Protection grade

KV

IP4X for the enclosure, and IP2X for doors of

compartments and circuit chambers

10

Busbar system

 

Single busbar, and single busbar segments

11

Operation mode

 

Electromagnetic and spring energy-storing