Remove Now
Cancle

Supply Customized 33kV Single Busbar Medium Voltage Switchgear

KYN61-40.5 Metal-clad withdrawable AC metal-enclosed switchgear is used for the complete distribution equipments of power plant, transformer and hydropower plant system. The device is equipped with “Five Preventions” functions.

Description

  • Place of Origin: Hunan, China (Mainland)
  • Brand Name: HNAC
  • Model Number: KYN28 KYN28A KYN61
  • Name: Customized 33kV Switchgear Medium Voltage Switchgear
  • Frequency: 50 HZ/60HZ
  • Design: Customized
  • Seismic intensity: not more than 8°C
  • Protection degree: IP4X for enclosure; IP2X for doors of compartments & circuit chambers
  • Main voltage range: 35KV/24KV/12KV/11KV/0.4KV
  • Main cabinet type: KYN28/KYN61/GGD/XGN15/...
  • Rated current: 630, 1250, 1600, 2000, 2500, 3150
  • Busbar system: Single busbar, and single busbar segments
  • Certificate: ISO9001

 

KYN61-40.5 Metal-clad withdrawable AC metal-enclosed switchgear is used for the complete distribution equipments of power plant, transformer and hydropower plant system. The device is equipped with “Five Preventions” functions.

Working voltage:26~40.5kV(50 / 60 Hz)              

Max. working voltage: 40.5kV

Max. rated current: 2000A

Rated short-time withstand current,4s: 20 / 25 / 31.5kA

Rated peak withstand current : 50 / 63 / 80 kA

Steel Enclosure: IP3X

Wide x deep x high:   1400mm x 2800mm x 2600mm                                                     

 


KYN28-24, KYN28A-12 Metal-clad withdrawable AC metal-enclosed switchgear is used for the complete distribution equipments of power plant, transformer and hydropower plant system. The device is equipped with “Five Preventions” functions.

 

KYN28-24

Working voltage: 13~24kV (50 / 60 Hz)

Max. working voltage: 24kV

Rated current: 1250 / 1600 / 2000 / 2500 / 3150A*(* With enforced cooling)

Rated short-time withstand current,4s: 20 / 31.5 / 40 kA

Rated peak withstand current : 63 / 80 / 100 kA

Steel Enclosure: IP4X

Wide x deep x high:   1000mm x 1800mm x 2300mm   

 

KYN28A-12

Working voltage: 3.6~12kV (50 / 60 Hz)

Max. working voltage: 12kV

Rated current:  630 / 1250 / 1600 / 2000 / 2500 / 3150A*(* With enforced cooling)

Rated short-time withstand current, 4s: 16 / 20 / 25 / 31.5 / 40 / 50 kA

Rated peak withstand current :40 / 50 / 63 / 80 / 100 / 125kA

Steel Enclosure: IP4X

 

Wide x deep x high:   800/1000mm x 1500 /1660mm x 2300mm

 

Ambient conditions

1, For the normal design, the  altitude should be not more than 1,000m. If  above 1,000m, it will design  according to the  altitude correction factor  of the  highland and manufacture as per the requirements suitable for the highland altitude.

2, The ambient  air temperature  ranges -35℃~+40℃, and  the average  temperature within 24h ≤ +35℃. If  exceeding the specified time, it  has to reduce the capacity  according to the actual condition;

3, The relative  humidity  should not  exceed 50%  at +40℃,  while  at lower  temperatures, larger  relative humidity  is acceptable,  e.g.  90% at  +20℃.  Considering the  change  of temperature may sometime cause the condensation, the daily average should be less than 95% and the monthly average less than 90%;

4, The  water  vapour   average  should  be ave2.2*10-3Mpa  or  below   while  the  monthlyrage not larger than  1.8*10-3Mpa;

5, The gradient between installation surface and vertical plane is ≤ 5°;

6, The seismic intensity should be not more than 8 degree;

7, Frequent severe violation is acceptable;

8, No pollution is  allowed to the ambient  air, such as corrosive  substance, flammable gas, vapour and so on.